WATEX Ltd.

Phone: +371 67 381 989
e-mail: info@watex.eu

Ganību dambis 27 K5,
Rīga, LV-1005, Latvija

 

RCMB Iron removal filter WATEX RCMB-10
RCMB Iron removal filter WATEX RCMB-10 RCMB Iron removal filter WATEX RCMB-10 RCMB Iron removal filter WATEX RCMB-10 RCMB Iron removal filter WATEX RCMB-10 RCMB Iron removal filter WATEX RCMB-10 RCMB Iron removal filter WATEX RCMB-10

Iron removal filter WATEX RCMB-10 (148)

WATEX

RCMB10

Price without VAT: 797.77 EUR

Summerhouse 

Private home 

Hotel

Plant 

Iron: At first, the water is clear, but when in contact with air, stained brown and form deposits on sanitary facilities. Metallic taste. Norm 0.2 mg / l. 

Manganese: At first, the water is clear, but when in contact with air, there is a dark shade and form a black precipitate on the sanitary facilities. Metallic taste. Often manganese is supplied with iron. The provision 0.05 mg / l. 

Smell: Just out of the tap to pour cold water felt a specific smell. It can be as foul eggs or swamp. 

Turbidity: Most often found in drinking water network, especially in times when water pipes are made repair or disconnecting, cleaning and so on. Clear water might contain floating particles that are visible. Turbidity in water is as unexpected, uninvited guest who may appear in the worst possible moments. If the filter will not be installed, all washes clothes could became dirty. As another example, it is unpleasant to take a shower in dirty, muddy water with bad odour. 

Number of consumers 2

Number of consumers 3

1 m³/h 

Without chemical reagents 

Oxidation with air 

Flow control 

Automatic 

Available at stock

Popular products 

Deluxe 

We make installation

Delivery specified  to your location and time 

Description

 WATER QUALITY PROBLEM

Iron and manganese often causes the main problem of the waterworks. When water gets in contacts with air, it changes the colour, turbidity increases and sediments appears. Water has a metallic taste. Water pipes are clogged and sanitation at the consumer becomes dirty. Suggested concentration of iron should be 0.1 mg/l and manganese 0.05mg/l.

 

SOLUTION

The best solution for this problem is oxidation and sand filtration. WATEX RCMB series filters are designed to purify water from turbidity, colorfulness, iron, manganese and odor for private houses. Mainly it is used for groundwater purification.

 

OPERATING PRINCIPLE

RCMB filter operating principle is based on aeration and filtration. When water is aerated, iron, manganese and mechanical impurities form sediment, which can be filtered. Suspended solids are filtered through filtering material, which has been poured in to filter. Filters depending on pollution levels and water consumption have to be rinsed regularly. Filters after rinsing are regenerated and can purify water. Equipment consists from reactor, filter and compressor.

 
PRESSURE TANK

Pressure filter tanks are made from fiberglass with inner PE coating that can hold pressure up to PN10.

 

FILTER MATERIAL        

For water purification filtering material AquaMandix and quartz sand with different grain size (0.4-0.8 mm, 0.7-1.25 mm, 1-3 mm, 3-5 mm) is being used. Porous structure of AquaMandix provides a large active surface and provides efficient adsorption and accumulation of sediment.

 
CONTROL UNIT  

The filter is equipped with an automatic Clack control which performs filtering and rinsing sequences automatically. Usually rinsing is performed at 2:00 at night.

 

AIR SUPPLY        

For water aeration it is necessary to  install air compressor. Air is injected in the water before it enters reactor.

 

PRECONDITIONS       

The equipment need sewer and electricity 220V connection, input water pressure with a minimum pressure of 2.5 bar, the room temperature above 0° C, the water temperature to 25° C as well as correct system connection.

 
SYSTEM MAINTENANCE       

Filters will provide with good quality water if operating personnel will ensure proper air supply, and unnecessary air removal and regular rinsing processes. Water purification system does not require specific chemical admixtures that have to be refilled.  

 

Additional equipment options:

  • Condensate isolation for tank;
  • By-pass valve – For easier assembly.

 

Technical parameters of equipment

Unit

Model

RCMB10

RCMB12

RCMB13

Flow rate Qnom

m3/h

0.8

1.0

1.3

The amount of water for regeneration

m3

0.11

0.13

0.17

Minimum flow rate for rinsing

m3/h

1.6

2.0

2.6

Tank size (diameter) 

inches

10

12

13

m

0.25

0.30

0.33

Tank volume

liters

64

85

110

The amount of filtering material

liters

43

57

73

Dimensions

 

 

 

 

Length

m

1.06

1.21

1.29

Width

m

0.25

0.30

0.33

Height

m

1.53

1.48

1.53

Connection. in /ext/kan.

inches

1”

1”

1”

Filtration

 

Iron, manganese, turbidity, odor, colorfulness

Tank material

 

FRP (fiberglass)

Filtering material

 

AquaMandix, silica sand 0.4x0.8 mm, 0.7x1.25 mm, 1x3 mm, 3x5 mm

Operating pressure

bar

2-6

Electric Connection

 

220V, 50Hz, 1 phase

Electricity consumption

W

3 W

  

Back to Top